Climate sensors
PASCAL-STVS-Z – Novasina
differential pressure sensor with and display for cleanroom applications: 0..50Pa / 0..200Pa
Differential pressure measuring instrument for cleanroom applications with automatic zero-point calibration for the monitoring of room pressure and filter saturation. The device disposes of a display as well as an integrated alarm switch contact.
Technical specifications
Measuring ranges: 0..50Pa or 0..200Pa
Accuracy: 0,15Pa (0..50Pa version) and 0,2Pa (0..200Pa version)
Power supply: 10,5..35VDC
Relays contacts: < 48VDC / VAC, < 60W
Dimensions: 119 x 68 x 29mm
Overpressure: max. 20 kPa
Indicator: 2 line display and 2 LED for alarm / 1 LED for status
Programming: configuration/calibration via software -PascalTool WIN